Pure Sine Wave Power Inverter
1.Aims at post, telecommunication,railway,elctric power,etc.
2.Adapt to systems intensive to power-line interference
Features:Inverter Parameters:
1.SPWM technology, pure sine wave output
2.CPU control, advanced anti-jamming technology, good electromagnetism compatibility
3.LCD+LED display, easy to operate
4.Vertical, 19 inch rack, power machine cabinet installation
5.Over-voltage, low-voltage, short-circuit, over-load protection
6.AC main supply, DC main supply, pure DC power supply
7.inverter parameters:
Model/series | NP800S | NP800D | NP800E |
Capacity | 1KVA~10KVA | 1KVA~20KVA | 1KVA~40KVA |
AC input | |||
Phase | Single-phase | ||
Voltage | 220V±20% | ||
Frequency | 50HZ±10% | ||
AC output | |||
Phase | Single-phase | ||
Voltage | 220 V±2%(On battery) | ||
Frequency | 50HZ±0.1%( On battery) | ||
Power factor | 0.8 | ||
Wave-form | Sine wave | ||
Crest factor | 3:1 | ||
Total voltage harmonics distortion | linear load <3%,non-linear load <5% | ||
Overload protection | >125%,1min;>150%,200ms | ||
Output voltage transient characteristic | ±5%( Load abrupt change From 0 to 100%) | ||
Transient response time | <20ms | ||
Conducted interference | 0.15~0.5MHz, quasi peak value <79dB, average value<66dB 0.5~30MHz, quasi peak value <73dB, average value<60dB | ||
DC input | |||
Rated DC voltage | 48V | 110V | 220V |
The range of DC voltage | 40-57V | 90-150V | 180-300V |
Adverse disturbance current | <10% | ||
System spec | |||
Protection | Overload, over charge and over discharge;out the range of voltage and frequency, over current, short circuit, over temperature ect. | ||
Full load efficiency | >85% | ||
Transfer time | <8ms | ||
Crest factor | 3:1 | ||
Communication interface | RS232 | ||
Environment temperature | 0-40°C | ||
Relative ambient humidity | 20%-90%(Non-condensing ) | ||
Altitude | <1500m, 1% rated capacity decrease against rised 100m | ||
Cooling method | Forced are-cooling with temperature control | ||
Noise | <60dB | ||
Isolation voltage | 1500Vac/1min, The terminal of input and output to earth, leakage current less than 3.5mA. |